Specifications:
Process Fluid :Display:
Liquid, Gas, Vapor 4 Digits programmable & 0-100% Bargraph
Application: Display Unit:
Differential Pressure, Gauge Pressure, Standard 22 engineering unit
Absolute Pressure 4 Digits programmable for special unit
Measuring Range: Keyboard:
( Minimum) 0 – 0.125 kPa ~ 0 – 1.5 kPa 3 keys from internal for Programming
( Maximum) 0 – 4.0 MPa ~ 0 – 25.0 MPa
Turn Down Ratio: Current Output:
1 : 100 4 – 20 mA 2 wires Hart Protocol
Accuracy:
+/- 0.075% of span Rohm=(Vdc-9)*50
Stability: Power Supply:
+/-0.15% of URL for 2 years 24 V DC
Working Temperature: Damping Adjustment:
-25 to +95 C 0 – 32 Second
Max. Pressure: Response Time:
40 MPa 200 ms
Material: Mounting:
Flange/Adapters Bracket on 2″ Pipe
Stainless Steel 304 / Stainless Steel Humidity Limits:
316 0 to 100% Relative Humidity
Drains/Vents Turn on Time:
Stainless Steel 304 / Stainless Steel 316 2 Seconds with minimum damping
Diaphragms Zero calibration:
Stainless Steel 316L / Hastelloy B / Automatic zero calibration by press button
Hastelloy C / Monel / Tantalum
Wetted O-Rings Electrical Connections:
Buna N / Viton / PTFE 1/4″ NPT ( M20 Conduit Threads )
Bolt s & Nut s Temperature Effect:
Carbon Steel / Stainless Steel 316 +/-0.18% of span per 20 C
Mounting Bracket Vibration Effect:
Carbon steel / Stainless Steel 304 / 316 +/-0.05% of URL per g to 200 Hz in any axis
Name / Tag Plate EMI/RFI Effect:
Stainless Steel 304 / Stainless Steel 316 Follow SAMA PMC 33.1 from 20 to 1000
Converter Housing MHz and for field strengths up to 30 V/m
Low copper cast aluminum alloy with Process connections:
polyurethane, light blue paint 1/4 – 18 NPT
Fill Fluid1/2 – 14 NPT( with Adapter )
Silicone / Fluorine Oil Ambient Temperature:
Enclosure:-25 to +80 C
IP65 Dimensions:
Intrinsically Safe: ia Ⅱ C T6 102 mm ( W ) * 188 mm ( H ) * 130 mm
Explosion proof: d ⅡB T5